Download Speeds Installation Time and Simplifies Wiring Wet Well Module

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Resistive opto-isolator wikipedia , lookup

Voltage optimisation wikipedia , lookup

Rectifier wikipedia , lookup

Power engineering wikipedia , lookup

History of electric power transmission wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Ohm's law wikipedia , lookup

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Stepper motor wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Mains electricity wikipedia , lookup

Earthing system wikipedia , lookup

Distribution management system wikipedia , lookup

Current source wikipedia , lookup

Buck converter wikipedia , lookup

Protective relay wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Wet Well Module
Speeds Installation Time and
Simplifies Wiring
Wet Well Module Reduces Complexity
The Wet Well Alarm Module substantially reduces the installation time
of a Mission M110 or M800 RTU. Share an existing high level float
with both the local control panel and the Mission Remote Terminal
Unit. A quick connect cable (RJ-45 ends) is included to link the Wet
Well Module to the Mission M110 or M800 RTU. Determine pump run
status with strap on current sensors. No more tapping into existing
high voltage alarm circuits or adding interposing relays.
High Wet Well Alarms Even When AC Has Failed
The Mission Wet Well Alarm Module is an exclusive, patented device
that can be added as an option to a M110 or M800 monitoring RTU.
The battery backed-up host RTU powers the wet well module. The
module goes between the pump station’s existing high level float and
the control panel enabling the RTU to detect and report high wet well
levels even when there is no AC power to the station! The module
relays the high wet well float closure to the existing control panel so
local alarm lights and buzzers continue to operate as before if the
pump station is under normal AC power. The built-in relays are “fail-safe”,
so if the module becomes disabled, the local alarms still function.
New Strap On
Current Sensor
• Reduce Installation Time
and Complexity
• High Wet Well Alarms Even
When AC Has Failed
Pump Run Times - Up to 3 Pumps
The module incorporates fast-installing strap-on current sensors that
allow the RTU to determine pump runs without interposing relays or
connections to high voltage conductors. Simply tie-wrap the current
sensor to one leg of the pump load conductors. Up to 3 pump runs
are supported on the board. Two current sensors are included. For
triplex lift stations, order a third sensor.
Current Sensor Avoids Direct Connections to High
Voltage Lines and Reliably Detects Pump Runnings
Direct wiring to the high voltage pump load circuit is eliminated,
resulting in a faster and safer installation. Unique strap-on current
sensors sense pumps running on the load legs going to pumps. This
direct sensing avoids misleading pump run indications. For example,
if the pump motor fails to run (open winding, circuit breaker tripped,
etc.) but the control circuit to motor starter is energized, the current
sensor would correctly report pump state as not running (no current
is flowing to the pump.) Other methods relying on the control circuit
would report the pump as running.
Class I, Div 2 Circuit for Hazardous Environments
Low-current and low-voltage are used to sense float status for Class I,
Div 2 compliance for hazardous environments.
• Pump Run State-Up to 3 Pumps
• Current Sensor Avoids Direct
Connection to High Voltage
Load and Reliably Detects
Pump Run State
• Class I, Div 2 Circuit for
Hazardous Environments
Wet Well Module
Details
Technical Specifications
Pump Runs Monitored:
• Up to 3, two current sensors included,
additional current sensor (PN499), and wiring
needed for 3rd pump
Pump Run Current:
• Greater than 5 amps sensed as “Pump Run”
• No maximum current limitation
Control Circuit Fuse:
To Control Panel
“Local Alarm”
• 5A @ 120 VAC
On Board LEDs:
Quick
Connect
RJ45 To
MISSION
RTU
Wet Well
Module
Motor
Starter
Relay 1
Power
Pump 1 Run
Pump 2 Run
Pump 3 Run
Float
Fuse Open
Motor
Starter
Relay 2
LED On Current Sensor:
Strap-on
Current
Sensor
• Current Flow
Optional Bypass Mode:
Included bypass switch disables control panel
supplied power to floats. Bypass when Class I,
Div 2 compliance is required AND control panel
supplies greater than 24 volts to float circuit.
Back-up functionality is disabled in bypass mode.
Includes:
• Wet Well Module with 2-position mounting
enclosure
• 2 current sensors
• Mounting hardware
• Cat 5 interconnect cable
• Two, 1-pair 22 gauge cables
• Instructions
Pump 2
Pump 1
High Level Float
(877) 993-1911 • sales@123mc.com • www.123mc.com
©2016 Mission Communications. The Mission Communications logo is property of Mission Communications.
All Rights Reserved. Protected under patents 7,216, 145. Specifications subject to change without notice.
Literature Code: WWMG2-0416