* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download NEC Articles
Ground (electricity) wikipedia , lookup
Electrification wikipedia , lookup
Electrical substation wikipedia , lookup
Electric power system wikipedia , lookup
History of electric power transmission wikipedia , lookup
Electronic engineering wikipedia , lookup
Power engineering wikipedia , lookup
Earthing system wikipedia , lookup
Opto-isolator wikipedia , lookup
Power over Ethernet wikipedia , lookup
Mains electricity wikipedia , lookup
Integrated circuit wikipedia , lookup
Alternating current wikipedia , lookup
Transmission tower wikipedia , lookup
Flexible electronics wikipedia , lookup
Electrical wiring in the United Kingdom wikipedia , lookup
Telecommunications engineering wikipedia , lookup
NFPA 70, NATIONAL ELECTRICAL CODE, NEC 2011 SIMTRA® SMART CABLE APPLICABLE NEC ARTICLES Code Standards herein are listed for reference only, including revisions by issuing authority, form a part of this specification section to the extent indicated. Standards listed are identified by issuing authority, authority abbreviation or acronym, designation number, title or other designation established by issuing authority. Standards subsequently referenced herein are referred to by issuing authority abbreviation and standard designation. Chapter 3 Wiring Methods and Materials Article 300 Wiring Methods 300.1 Scope. (A) All Wiring Installations. This article covers wiring methods for all wiring installations unless modified by other articles. 300.2 Limitations. (A) Voltage. Wiring methods specified in Chapter 3 shall be used for 600 volts, nominal, or less where not specifically limited in some section of Chapter 3. They shall be permitted for over 600 volts, nominal, where specifically permitted elsewhere in this Code. 300.3(C) Conductors of Different Systems. (1) 600 Volts, Nominal, or Less. Conductors of ac and dc circuits, rated 600 volts, nominal, or less, shall be permitted to occupy the same equipment wiring enclosure, cable, or raceway. All conductors shall have an insulation rating equal to at least the maximum circuit voltage applied to any conductor within the enclosure, cable, or raceway. Informational Note No. 1: See 725.136(A) for Class 2 and Class 3 circuit conductors. Clarification note: National Electrical Code Handbook 2011. Section 300.3(C)(1) makes it clear that the maximum circuit voltage in the raceway, not the maximum insulation voltage rating of the conductors in the raceway, is what determines the minimum voltage rating required for the insulation of the conductors for systems of 600 volts or less. Article 330 Metal-Clad Cable: Type MC 330.1 Scope. This article covers the use, installation, and construction specifications of metal-clad cable, Type MC II. Installation 330.10 Uses Permitted. (A)(2) For power, lighting, control and signal circuits. (B) Specific Uses. Type MC cable shall be permitted to be installed in compliance with Parts II and III of Article 725 and 770.133 as applicable and in accordance with 330.10(B)(1) through (B)(4). 1 Article 334 Nonmetallic-Sheathed Cable: Types NM, NMC, and NMS 334.1 Scope. This article covers the use, installation, and construction specifications of nonmetallic-sheath cable. 334.2 Definitions. Nonmetallic-Sheathed Cable. A factory assembly of two or more insulated conductors enclosed within an overall nonmetallic jacket. Type NM. Insulated conductors enclosed within an overall nonmetallic jacket. Type NMS. Insulated power or control conductors with signaling, data, and communications conductors within an overall nonmetallic jacket. 334.6 Listed. Type NM, Type NMC, and Type NMS cables shall be listed. II. Installation 334.10 Uses Permitted. Type NM, Type NMC, and Type NMS cables shall be permitted to be used in the following: (5) Types I and II construction where installed within raceways permitted to be installed in Types I and II construction. III. Construction Specifications 334.100 Construction. The outer cable sheath of nonmetallic-sheathed cable shall be a nonmetallic material. 334.104 Conductors. The 600-volt insulated conductors shall be sizes 14 AWG through 2 AWG copper conductors or sizes 12 AWG through 2 AWG aluminum or copper-clad aluminum conductors. The communications conductors shall comply with Part V of Article 800. 334.112 Insulation. The insulated power conductors shall be one of the types listed in Table 310.104(A) that are suitable for branch-circuit wiring or one that is identified for use in these cables. Conductor insulation shall be rated at 90C (194F). Informational Note: Types NM, NMC, and NMS cable identified by markings NM-B, NMC-B, and NMS-B meet this requirement. 334.116 Sheath. The outer sheath of the nonmetallic-sheath cable shall comply with 334.116(A), (B), and (C). 2 (A) Type NM. The overall covering shall be flame retardant and moisture resistant. (B) Type NMC. The overall covering shall be flame retardant, moisture resistant, fungus resistant, and corrosion resistant. (C) Type NMS. The overall covering shall be flame resistant and moisture resistant. The sheath shall be applied so as to separate the power conductors from the communications conductors. Article 336 Power and Control Cable: Type TC 336.1 Scope. This article covers the use, installation, and construction specifications for power and control tray cable. Type TC. II. Installation 336.10 Uses Permitted. Type TC cable shall be permitted to be used as follows: (5) For Class 1 Circuits as permitted in Parts II and III of Article 725. Chapter 7 Special Conditions Article 725 Class 1, Class2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits 725.1 Scope. This article covers remote-control, signaling, and power-limited circuits that are not an integral part of a device or appliance. 725.136 Separation from Electric Light, Power, Class 1, Non-Power-Limited Fire Alarm Circuit Conductors, and Medium-Power Network-Powered Broadband Communications Cables. (B) Separated by Barriers. Class 2 and Class 3 circuits shall be permitted to be installed together with the conductors of electric light, power, Class 1, non-power-limited fire alarm and medium power network-powered broadband communications circuits where they are separated by a barrier. (I) Other Applications. (1) Either (a) all of the electric light, power, class 1, non-power-limited fire alarm and mediumpower network powered broadband communications circuit conductors or (b) all of the Class 2 and Class 3 circuit conductors are in a raceway or in metal-sheathed, metal-clad, non-metallicsheathed, or Type UF cables. (2) All of the electric light, power, Class 1 non-power-limited fire alarm, and medium-power network-powered broadband communications circuit conductors are permanently separated from all of the Class 2 and Class 3 circuit conductors by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the conductors. 3 Article 760 Fire Alarm Systems 760.1 Scope. This article covers the installation of wiring and equipment of fire alarm systems including all circuits controlled and powered by the fire alarm system. 760.136 Separation from Electric Light, Power, Class 1, NPLFA, and Medium-Power Network-Powered Broadband Communications Circuit Conductors. (B) Separation by Barriers. Power-limited fire alarm circuit cables shall be permitted to be installed together with Class 1, non-power-limited fire alarm, and medium-power networkpowered broadband communications circuits where they are separated by a barrier. (G) Other Applications. (1) Either (a) all of the electric light, power, class 1, non-power-limited fire alarm and mediumpower network powered broadband communications circuit conductors or (b) all of the powerlimited fire alarm circuit conductors are in a raceway or in metal-sheathed, metal-clad, nonmetallic-sheathed, or Type UF cables. (2) All of the electric light, power, Class 1 non-power-limited fire alarm, and medium-power network-powered broadband communications circuit conductors are permanently separated from all of the power-limited fire alarm circuit conductors by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the conductors. Article 770 Optical Fiber Cables and Raceways 770.1 Scope. The provisions of this article apply to the installation of optical fiber cables, raceways, and cable routing assemblies. This article does not cover the construction of optical fiber cables and raceways. 770.2 Definitions. Composite Optical Fiber Cable. A cable containing optical fibers and current-carrying electrical conductors. 770.3 Other Articles. (B) Composite Cables. Composite optical fiber cables shall be classified as electrical cables in accordance with the type of electrical conductors. They shall be constructed, listed, and marked in accordance with the appropriate article for each type of electrical cable. 770.133 Installation of Optical Fibers and Electrical Conductors. (A) With Conductors for Electric Light, Power, Class 1, non-Power-Limited Fire Alarm, or Medium Power Network-Powered Broadband Communications Circuits. When optical fibers are within the same composite cable for electric light, power, Class 1, non-power-limited fire alarm, or mediumpower network-powered broadband communications circuits operating at 600 volts or less, they shall be permitted to be installed only where the functions of the optical fibers and electrical conductors are associated. Nonconductive optical fiber cables shall be permitted to occupy the same cable tray or raceway with conductors for electric light, power, Class 1, non-power-limited 4 fire alarm, Type ITC, or medium-power network-powered broadband communications circuits, operating at 600 volts or less. Exception No. 5: Where all of the conductors of electric light, power, class 1, non-power-limited fire alarm, and medium-power network-powered broadband communications circuits are separated from all of the optical fiber cables by a permanent barrier or listed divider. Chapter 8 Communication Systems Article 800 Communications Circuits 800.1 Scope. This article covers communications circuits and equipment. 800.2 Definitions. Communication Circuit. The circuit that extends voice, audio, video, data, interactive services, telegraph (except radio), outside wiring for fire alarm and burglar alarm from the communications utility to the customer's communications equipment up to and including terminal equipment such as a telephone, fax machine, or answering machine. V. Installation Methods Within Buildings 800.110 Raceways for Communications Wires and Cables. (A) Types of Raceways. Communications wire and cables shall be permitted to be installed in any raceway that complies with either (A)(1) or (A)(2). (1) Raceways Recognized in Chapter 3. Communications wires and cables shall be permitted to be installed in any raceway included in chapter 3. The raceway shall be installed in accordance with the requirements of Chapter 3. (2) Other Permitted Raceways. Communication wires and cables shall be permitted to be installed in listed plenum communications raceway, listed riser communications raceway, or listed general-purpose communications raceway selected in accordance with provisions of 800.113, and installed in accordance with 362.24 trough 362.56, where requirements applicable to electrical nonmetallic tubing apply. 800.133 Installation of Communications Wires, Cables, and Equipment. (A) Separation from Other Conductors (1) In Raceway, Cable Trays, Boxes, Cables, and Enclosures (d) Electric Light, Power, Class 1, Non-Power-Limited Fire Alarm, and Medium-Power NetworkPowered Broadband Communications Circuits in Raceways, Compartments, and Boxes. Communications conductors shall not be placed in any raceway, compartment, outlet box, junction box, or similar fitting with conductors of electric light, power, Class 1, non-power-limited fire alarm, or medium-power network-powered broadband communication circuits. Exception No. 1: Where all the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium-power network-powered broadband communications circuits are separated from all of the conductors of communications circuits by a permanent barrier or listed divider. 5 (2) Other Applications. Communications wire and cables shall be separated at least 50 mm (2 in.) from the conductors of electric light, power, Class 1, non-power-limited fire alarm, or mediumpower network-powered broadband communications circuits. Exception No. 1: Where either (1) all the conductors of the electric light, power, Class 1, nonpower-limited fire alarm, and medium-power network-powered broadband communications circuits are in a raceway or in metal sheathed, metal-clad, nonmetallic-sheathed, Type AC, or Type UF cables, or (2) all of the conductors of communications circuits are enclosed in raceway. Exception No. 2: Where the communications wires and cables are permanently separated from the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium-power network-powered broadband communications circuits by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the wire. VI. Listing Requirements 800.179 Communication Wires and Cables. Communications wire and cables shall be listed in accordance with 800.179(A) through (I) and marked in accordance with Table 800.179. Conductors in communications cables, other than in a coaxial cable, shall be copper. Communications wire and cables shall have a voltage rating of not less than 300 volts. The insulation for the individual conductors, other than the outer conductor of a coaxial cable, shall be rated for 300 volts minimum. The cable voltage rating shall not be marked on the cable or on the under carpet communications wire. Communications wires and cables shall have a temperature rating of not less than 60C. (A) Type CMP. (B) Type CMR. (C) Type CMG. (D) Type CM. (E) Type CMX. (G) Communications Circuit Integrity (CI) Cables. Cables suitable for use in communications systems to ensure survivability of critical circuits during a specified time under fire conditions shall be listed as circuit integrity (CI) cable. Cables identified in 800.179(A) through (E) that meet the requirements for circuit integrity shall have the additional classification using the suffix "CI". (H) Communications Wires. Communications wires, such as distributing frame and jumper wire, shall be listed as being resistant to the spread of fire. (I) Hybrid Power and Communications Cables. Listed hybrid power and communications cables shall be permitted where the power cable is a listed Type NM or NM-B conforming to the provisions of Article 334, and the communications cable is listed Type CM, the jackets on the listed NM or NM-B and listed CM cables are rated for 600 volts minimum, and the hybrid cable is listed as being resistant to the spread of fire. Article 820 Community Antenna Television and Radio Distribution Systems 820.1 Scope. 6 This article covers coaxial distribution of radio frequency signals typically employed in community antenna television (CATV) systems. V. Installation Methods Within Buildings. 820.110 Raceways for Coaxial Cables. (A) Types of Raceways. Coaxial cables shall be permitted to be installed in any raceway that complies with either (A)(1) or (A)(2). (1) Raceways Recognized in Chapter 3. Coaxial cables shall be permitted to be installed in any raceway included in chapter 3. The raceway shall be installed in accordance with the requirements of Chapter 3. (2) Other Permitted Raceways. Coaxial cables shall be permitted to be installed in listed plenum communications raceway, listed riser communications raceway, or listed general-purpose communications raceway selected in accordance with provisions of 820.113, and installed in accordance with 362.24 trough 362.56, where requirements applicable to electrical nonmetallic tubing apply. 820.133 Installation of Coaxial Cables and Equipment. (A) Separation from Other Conductors. (1) In Raceways, Routing Assemblies, Cable Trays, Boxes, and Enclosures. (C) Electric Light, Power, Class 1, Non-Power-Limited Fire Alarm, and Medium-Power NetworkPowered Broadband Communications Circuits. Coaxial cable shall not be placed in any raceway, compartment, outlet box, junction box, or other enclosures with conductors of electric light, power, Class 1, non-power-limited fire alarm, or medium-power network-powered broadband communication circuits. Exception No. 1: Where all the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium-power network-powered broadband communications circuits are separated from all of the coaxial cables by a permanent barrier or listed divider. (2) Other Applications. Coaxial cables shall be separated at least 50 mm (2 in.) from the conductors of electric light, power, Class 1, non-power-limited fire alarm, or medium-power network-powered broadband communications circuits. Exception No. 1: Where either (1) all the conductors of the electric light, power, Class 1, nonpower-limited fire alarm, and medium-power network-powered broadband communications circuits are in a raceway or in metal sheathed, metal-clad, nonmetallic-sheathed, Type AC, or Type UF cables, or (2) all of the conductors of coaxial cables are enclosed in raceway. Exception No. 2: Where the coaxial cables are permanently separated from the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium-power network-powered broadband communications circuits by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the wire. Article 830 Network-Powered Broadband Communications Systems 830.1 Scope. 7 This article covers network-powered broadband communications systems that provide any combination of voice, audio, video, data, and interactive services through a network interface unit. V. Installation Methods Within Buildings. 830.110 Raceways for Low-Powered and Medium-Powered Network-Powered Broadband Communications Cables. (A) Raceways Recognized in Chapter 3. Low - and medium-power network-powered broadband communications cables shall be permitted to be installed in any raceway included in Chapter 3. The raceway shall be installed in accordance with the requirements of Chapter 3. (B) Raceway Fill for Network-Powered Broadband Communications Cables. Raceway fill for network-powered broadband communications cables shall comply with either (B)(1) or (B)(2). (1) Low-Power Network-Powered Broadband Communications Cables. The raceway fill requirements for Chapter 3 and 9 shall not apply to low-powered broadband communications cables. (2) Medium-Power Network-Powered Broadband Communications Cables. Where medium-power network-powered broadband communications cables are installed in a raceway, the raceway fill requirements of Chapter 3 and 9 shall apply. 830.133 Installation of Network-Powered Broadband Communications Cables and Equipment. Cable and equipment installations within buildings shall comply with 830.133(A) through (C), as applicable. (A) Separation from Other Conductors (1) In Raceway, Cable Trays, Boxes, and Enclosures (f) Electric Light, Power, Class 1, Non-Powered Broadband Communications Circuit Cables. Network-powered broadband communications cable shall not be placed in any raceway, cable tray, compartment, outlet box, junction box, or similar fittings with conductors of electric light, power, Class 1, or non-power-limited fire alarm circuit cables. Exception No. 1: Where all the conductors of electric light, power, Class 1, non-power-limited fire alarm circuits are separated from all of the network-powered broadband communications cables by a permanent barrier or listed divider. (2) Other Applications. Network-powered broadband communications cables shall be separated at least 50 mm (2 in.) from the conductors of electric light, power, Class 1, non-power-limited fire alarm circuits. Exception No. 1: Where either (1) all the conductors of the electric light, power, Class 1, nonpower-limited fire alarm circuits are in a raceway or in metal sheathed, metal-clad, nonmetallicsheathed, Type AC, or Type UF cables, or (2) all of the network-powered broadband communications cables are enclosed in raceway. Exception No. 2: Where the network-powered broadband communications cables are permanently separated from the conductors of electric light, power, Class 1, non-power-limited fire alarm circuits by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the wire. 8 NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and PowerLimited Circuits This article covers the installation of remote control, signaling, and power-limited circuits that are not an integral part of a device or appliance. Also provides safeguards to limit the amount of energy that can be introduced into low-voltage components and circuits and provides requirements related to the products of combustion and flame-spread ratings for signaling systems and remote-control wiring. To know when to use the requirements for control, signaling, and power-limited circuits we should know the following descriptions: Remote-Control Circuit Any electrical circuit that controls any other circuit through a relay or an equivalent device. Signaling Circuit Any electrical circuit that energizes signaling equipment. Circuit Classification Circuit classification is based primarily on the circuit power supply. The classes of circuits are divided into Class 1, Class 2, and Class 3 and are classified as remote control, signaling, and power-limited circuits by the NEC. These circuits are differentiated by their function and power limitation, which isolates them from lighting and power circuits. Also these circuits are categorized according with their specific voltage and power limitations. Class 1 Circuit The portion of the wiring system between the load side of the over current device (fuse or circuit breaker) or power-limited supply and the connected equipment. Class 1 circuits shall comply with Part I and II of the NEC article 725. Class 1 circuits are classified either as power-limited circuits and shall comply with the power limitations of the NEC Section 725.41.(a) or they are classified as remote control and signaling circuits and shall comply with the power limitations of the NEC Section 725.41.(b). Insulation on conductors for Class 1 circuits is required to be suitable for 600 volts. Conductors larger than No. 16 shall comply with the requirements of NEC Article 310. Class 1 Power-Limited Circuits These circuits are used for functions other than signaling or remote control. These circuits shall be permitted to be either AC or DC and shall be supplied from a source that has a rated output of not more than 30 volts and 1000 volt-amperes. These circuits are provided with a current limiter on the power source that supplies them. This limiter is an over current device (fuse or circuit breaker) or power-limited supply (transformer) that restricts the amount of supplies current on the circuit in the event of an overload, short circuit, or ground-fault. Typical use of Class 1 Power-Limited circuits: Low-voltage under counter lighting system, 24 volt circuit used to operate low-voltage damper motors to control environmental airflow. Class 1 Remote-Control Circuits These circuits are used to control another circuit through a relay or equivalent device. These circuits shall not exceed 600 volts. The power output of the source is not required to be power limited. These circuits shall satisfy the majority of the same wiring requirements for power and light circuits. Typical use of Class 1 Remote-Control Circuits: Elevators, conveyors, 120 volt circuit that operates the coil of a motor starter or lighting contractor, the 24 volt circuit for a garage door, 9 motor controllers which operate mechanical process, shunt-trip circuits for circuit breakers, equipment controlled from one or more location. Class 1 Signaling Circuits These circuits are used to energize signaling equipment. These circuits shall not exceed 600 volts. The power output of the source is not required to be power limited. These circuits shall satisfy the majority of the same wiring requirements for power and light circuits. Typical use of Signaling Circuits: Doorbells, buzzers, signal lights, annunciators, burglar alarm, electric clock system, factory call system, listed nurse call system with a power supply with an output of 500 watts at 24 volts, and other detection indication or alarm devices. Class 2 Circuit The portion of the wiring system between the load side of a Class 2 power source and the connected equipment. Due to its power limitations, a Class 2 circuit considers safety from a fire initiation standpoint and provides acceptable protection from electric shock. In general, a Class 2 circuit work at 30 volts or less with a power supply not exceeding 100 VA, and the current to 5mA for circuits over 30 volts. See NEC Chapter 9, Table 11(A) where provides the power limitations for the power source. Class 2 circuits shall comply with NEC Article 725 Parts I and III, which are referenced by FPN No.2 to 725.52. Typical use of Class 2 Circuits: Circuits used to interconnect computers for the intention of transfer data, thermostats for heating system, small bell or buzzer system, annunciators systems, small intercom phone systems in which a battery and the ringing circuit supply the voice circuit. A dry cell battery shall be considered an inherently limited Class 2 power source, provided the voltage is 30 volts or less and the capacity is equal to or less than that available from series connected No, 6 carbon zinc cells. Class 3 Circuit The portion of the wiring system between the load side of a Class 3 power source and the connected equipment. Due to its power limitations, a Class 3 circuit considers safety from a fire initiation standpoint. Since higher levels of voltage and current than for Class 2 are permitted, additional safeguards are specified to provide protection from an electric shock hazard that could be encountered. In general, a Class 3 circuits are used when the power demand exceeds 0.50 VA and the power supply not exceeding 100 VA, for circuits over 30 volts. See NEC Chapter 9, Table 11(B) where provides the power limitations for the power source. Class 3 circuits shall comply with NEC Article 725 Parts I and III, which are referenced by FPN No.2 to 725.52. Typical use of Class 3 Circuits: Circuits used to interconnect computers for the intention of transfer data, Class 3 circuitry and accessories can be designed to alleviate the problem of excessive voltage drop, hospital nurse call system with a power supply rated at 100 VA and 100 volts. Building Construction Types All buildings are classified according to their construction type. Type I is least combustible and Type V is most combustible. The more combustible a building is and the more hazardous the use is, the more the maximum allowable area is limited. All construction types and use groups are allowed to have increased areas by using sprinklers. Building Construction Type I Type I construction is fire-resistive with non-combustible construction materials. This type of construction is for “all occupancy type” and can be of unlimited height (Commonly found in highrise buildings, Group 1 occupancies, mid-rise office and Group R Buildings). Typically these are concrete frame buildings made of noncombustible materials. All of the building elements (structural frame, bearing walls, floors and roofs) are fire resistance rated. 10 Building Construction Type II Type II construction has 3 categories with non-combustible construction materials, fire-resistive, one-hour rated, and non-rated. The number of “stories” permitted varies from 2 to 12, depending in the category rated (Commonly found in newer school buildings, commercial buildings, etc.). These buildings are constructed of noncombustible materials. Typically these are masonry bearing walls structures with steel studs for walls and steel bar joists for floor and roof structures. IIA has fire rated building elements (structural frame, bearing walls, floors and roofs). IIB is the most common construction type for commercial buildings because the building elements are not required to be fire resistance rated but still must be non-combustible. Building Construction Type III Type III construction has 2 categories with protected combustible or unprotected combustible construction materials, non-rated, non-rated with sprinkler, one-hour rated, and one-hour rated with sprinkler. The number of “stories” permitted varies from 4 to 5, depending in the category rated commonly found in “warehouse districts of older cities, multifamily dwellings buildings, etc. Type III construction is the type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by the code (combustible or non-combustible). This is typical of buildings with masonry bearing walls and wood roofs or floors. Building Construction Type IV Type IV has 1 category with heavy timber and heavy timber with sprinkler. The number of “stories” permitted varies from 4 to 5 depending in the category rated (commonly found in multifamily dwellings buildings, etc.). This is Heavy Timber construction which is not common except perhaps in some worship facilities. Building Construction Type V Type V construction has 2 categories with protected wood frame or unprotected wood frame construction materials, non-rated, non-rated with sprinkler, one-hour rated, and one-hour rated with sprinkler. The number of “stories” permitted varies from 2 to 4, depending in the category rated (commonly found in newer apartment buildings, etc.). Type V construction is typically wood frame construction. V-A requires fire rated assemblies for all building elements (structural frame, bearing walls, floors and roofs); this is often seen in older construction that predates sprinklers but still not commonly used. V-B is very common because it does not require any fire rating. 11